EasyManua.ls Logo

Kidde Stratos-HSSD 2 - 5.4 Power Supply Connections

Kidde Stratos-HSSD 2
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 32
Stratos HSSD-2 INSTALLERS HANDBOOK Iss. 12
5.4.2 Command
Module power supply
connections
5.4.1 Detector power
supply connections
5.4 Power Supply
Connections
0V
Safety earth*
+ 24V DC
0V
Safety earth*
+ 24V DC
*Note: the safety earth connection must be
separate and not connected to the GND
(ØV) connection.
The detector may be powered by any EN54-4 compliant monitored 24DC power
supply of sufficient capacity.
0V
Safety earth*
+ 24V DC