Page 37
Stratos HSSD-2 • INSTALLER’S HANDBOOK • Iss. 12
The device object supports the following
Properties:
Object_Identifier
Object_Name
Object_Type
System_Status
Vendor_Name
Vendor_Identifier
Model_name
Firmware_Revision
Application_Software_Version
Protocol_Version
Protocol_Conformance_Class
Protocol_Services_Supported
Protocol_Object_Types_Supported
Max_APDU_Length_Accepted
Segmentation_Supported
APDU_Timeout
Number_Of_APDU_Retries
For further information on BACnet implementation, contact the Help Line. (see page 3)
6.1.3 Paging from the Command Module
The Stratos-HSSD 2 Command Module has the facility to send text messages to
alphanumeric pagers or SMS messages to some mobile phones.
In order to send messages to a pager or similar device a modem must be plugged into
the RS232TX and RS232RX terminals of the Command Module using a suitable cable.
The call centres of the pager or SMS-capable phone must support the TAP protocol. In
the UK Cellnet phones and BT pagers have this facility, amongst others. Please contact
your pager provider to check whether they provide access with the TAP protocol.
The following Properties are supported
by the analogue value objects:
Object_Identifier
Object_Name
Object_Type
Present_Value
Status_Flags
Event_State
Out_Of_Service
Units
6.1.2 BACnet support (protocol 2)
The Command Module models the attached detectors as analogue value object types
instances 2 to 128. The Command Module status is stored as analogue value instance
1. The Present_Value property of the analogue objects can have one of the following
values; 0 = Disabled; 2 = Fault; 32 = Normal; 48 = PreAlarm; 64 = Fire 1; 128 = Fire 2.