Chapter 2: Front panel programming
P/N 3102351-EN • REV 005 • ISS 28DEC18 111
6. Press the Menu button to exit menu mode, or continue programming.
CMS network (transmitter) programming
Note: Connecting to a central monitoring station (CMS) using a TCP/IP Ethernet network does
not comply with CAN/ULC S559 3
rd
edition requirements.
The information programmed here pertains to the central monitoring station (CMS) network
that the control panel uses to communicate with the CMS. This is a TCP/IP Ethernet network.
Event information is sent to the CMS just as it is when using a dialer; however, the
transmission is over an Ethernet network rather than the telephone lines.
To program the panel for network reporting, you must install and enable the optional SA-ETH
Ethernet module. Once installed, program only the network card connected to a compatible
network receiver, as listed in the appropriate compatibility guide.
Obtain the following information from the central monitoring station’s network administrator:
• An IP address
• Port number
• Receiver number
• Line number
Notes
• CID is the only format that can be transmitted to the CMS over an Ethernet network.
• You must enter a different port number for each account. If you enter the same port number
for multiple accounts, the panel will enable one account and disable all others.
• No two accounts can have the same IP address or port number.
• Outputs activation state will not be sent to CMS.
Table 34: CMS network (transmitter) programming options
Description
Yes: Enables the CMS network operation
No: Disables the CMS network operation
Enter the CMS account’s four-digit hexadecimal ID code (0000 to FFFF). FFFF is not
valid and must be changed.
Enter the IP address for the CMS.
Enter the port address for the CMS (0 to 65535, 1024 is not allowed).
Set send restorals to:
Yes: Sends off-normal event restorals to the monitoring facility DACR
No: Does not send off-normal event restorals to the monitoring facility DACR