Chapter 3: System operation 
158  P/N 3102351-EN • REV 005 • ISS 28DEC18 
  ID 
Loop 4 unconfigured alarm
  034 
Loop 1 unconfigured trouble
  005 
Loop 2 unconfigured trouble
  015 
Loop 3 unconfigured trouble
  025 
Loop 4 unconfigured trouble
  035 
 
To disable or enable a loop event: 
1.  Press the Menu button and choose Control. 
2.  Enter a level one password. 
3.  Choose Enable/Disable. 
4.  Choose Loop Event. 
5.  Select the loop event type that you want to disable or enable. 
See “Event ID numbers and descriptions” on page 142 for event descriptions and the list 
above for the events that can be disabled. 
6.  Press Enter. 
7.  Press Cancel to return to the previous menu. 
— or — 
Press the Menu button to exit menu mode. 
Disabling and enabling panel NACs 
Disabling a panel NAC prevents activations from being displayed, printed, or reported off 
premises. This is typically done during maintenance. Remember to enable the NAC as soon as 
you have finished working. 
NACs that have been disabled are not restored when the panel is reset. They must be enabled 
and then restored. 
NACs configured as latched output devices are not restored when the panel is reset. They 
must be manually unlatched and then restored. 
When you disable a panel NAC: 
•  The common Disable LED turns on 
•  The LCD displays a message indicating that the NAC is disabled 
•  The disabled and active points indicators on the LCD increment 
•  The common Trouble LED flashes and the panel goes into a trouble state 
•  The common Trouble relay changes state.