Chapter 3: System operation
P/N 3102351-EN • REV 005 • ISS 28DEC18 141
Internal event (panel or loop event)
MON ACT | 18:00:18 01/01/2007 E:010
Loop 2 Initializing
Where:
MON ACT = Monitor event
18:00:18 01/01/2007 = Time and date the event took place
E:010 = Event 010 (see “Event ID numbers and descriptionson page 142)
Loop 2 initializing = Label (could be the default label or a custom label)
Zone event
ALRM ACT | 18:00:34 01/01/2007 Z:008
Zone 08
Where:
ALRM ACT = Alarm event
18:00:34 01/01/2007 = Time and date the event took place
Z:008 = Zone 08
Zone 08 = Label (could be the default label or a custom label)
Device event
ALRM ACT | 18:00:34 01/01/2007 L:1 D:124
Loop 1 Device 124
Where:
ALRM ACT = Alarm event
18:00:34 01/01/2007 = Time and date the event took place
L:1 = Loop 1
D:124 = Device 124
Loop 1 Device 124 = Label (could be the default label or a custom label)