Appendix D: Device types to personality codes correlation
P/N 3102351-EN • REV 005 • ISS 28DEC18 245
Model
Device type
Personality code
RZI
Genesis Audible Silence
(25) Signal - supervised auto sync output (Class B)
RZI
Genesis Audible Visible Silence
(25) Signal - supervised auto sync output (Class B)
RZI
Genesis Non
-Silenceable (25) Signal - supervised auto sync output (Class B)
RZI
Relay Non
-Silenceable (8) Signal - dry contact output
RZI
Relay Non
-Silenceable (Latched) (8) Signal - dry contact output
SD
Duct Alarm
(1) Alarm - NO latching (Class B)
SD
Duct Supervisory Latching
(4) Active - NO latching (Class B)
SD
Duct Supervisory Nonlatching
(3) Active - NO nonlatching (Class B)
T
3T4
Auto Sync Output Non
-Silenceable (70) Unsupervised Relay Output
T3T4
Auto Sync Output Silenceable
(70) Unsupervised Relay Output
UM
2Wire Alarm
(13) Alarm - two-wire smoke unverified (Class B)
UM
2Wire Alarm Class A
(20) Alarm - two-wire smoke unverified (Class A)
UM
2Wire Alarm Verify
(14) Alarm - two-wire smoke verified (Class B)
UM
2Wire Alarm Verify Class A
(21) Alarm - two-wire smoke verified (Class A)
UM
Alarm
(1) Alarm - NO latching (Class B)
UM
Alarm Class A
(9) Alarm - NO latching (Class A)
UM
Continuous Non
-Silenceable (16) Signal - supervised output (Class B)
UM
Continuous Non
-Silenceable (Latched)
(16) Signal - supervised output (Class B)
UM
Continuous Non
-Silenceable Class A (15) Signal - supervised output (Class A)
UM
Continuous Non
-Silenceable Class A
(Latched)
(15) Signal - supervised output (Class A)
UM
Continuous Silenceable
(16) Signal - supervised output (Class B)
UM
Continuous Silenceable Class A
(15) Signal - supervised output (Class A)
UM
Heat
(1) Alarm - NO latching (Class B)
UM
Heat Class A
(9) Alarm - NO latching (Class A)
UM
Monitor
(3) Active - NO nonlatching (Class B)
UM
Monitor Class A
(11) Active - NO nonlatching (Class A)
UM
None
(0) No Personality
UM
Pull Station
(1) Alarm - NO latching (Class B)
UM
Pull Station Class A
(9) Alarm - NO latching (Class A)
UM
Relay Non
-Silenceable (8) Signal - dry contact output
UM
Relay Non
-Silenceable (Latched) (8) Signal - dry contact output
UM
Relay Silence
(8) Signal - dry contact output
UM
Remote AC Fail
(3) Active - NO nonlatching (Class B)
UM
Remote AC Fail Class A
(11) Active - NO nonlatching (Class A)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde VS4 and is the answer not in the manual?

Kidde VS4 Specifications

General IconGeneral
BrandKidde
ModelVS4
CategoryFire Alarms
LanguageEnglish

Related product manuals