Chapter 2: Front panel programming
84 P/N 3102351-EN • REV 005 • ISS 28DEC18
Using fast groups
Note: To meet the UL\ULC requirement that evacuation signals activate within 10 seconds,
assign sounder base detectors to “fast” correlation groups.
See “Programming fast groups for sounder bases” on page 89.
If you are new to correlation group programming, see “What is a zone?” on page 37.
Adding members to correlation groups
Correlation groups can include zones, NACs, devices, unconfigured alarm events, and the
common trouble event. See the following procedure.
To add or remove members from a correlation group:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2 password.
3. Choose Correlation Groups and enter the correlation group number to be programmed.
(Values range from 001 to 199.)
4. Choose:
• Add/Remove Zone to add or remove a zone
• Add/Rem Panel NAC to add or remove a NAC
• Add/Rem Device to add or remove a device
Note: The Add/Rem device includes primary sensor, secondary sensor, and base, if
applicable.
• Add/Rem Panel Event
• Suite Sig Sil
• Activation Count
• Delay
• Copy
• Remove All
• Save
5. Enter the loop number (if the panel has multiple loops).
6. Enter the zone, NAC, or device number.
7. On the Status line, press Enter to select Included or Excluded:
• “Included” adds the item to the group
• “Excluded” removes the item from the group
8. Repeat steps 4 to 7 to add or remove other devices, zones, or NACs.
9. Repeat steps 3 to 9 to program additional correlation groups.
10. Press the Menu button to exit menu mode, or continue programming.