Chapter 2: Front panel programming
88 P/N 3102351-EN • REV 005 • ISS 28DEC18
are activated after the reset duration and an additional delay time assigned to the
correlation group, provided the device triggering the output device is still active.
When you configure a correlation group to activate, restore, or disable with the common
outputs assigned to reset activate or restore, the priorities are defined from highest to lowest,
as shown below.
1. Device disable (command menu or user key)
2. A latched output
3. Activation or restore via command menu
4. Restore via user key
5. Activation via user key
6. Restore from correlation (reset restore)
7. Activation via correlation
To add or remove a panel event:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2 password.
3 Choose Loop Configuration.
4. Choose Correlation Groups and enter the number of the correlation group. (Values range
from 001 to 199.)
5. Choose Add/Rem Panel Event.
6. Select:
Yes to add a panel event
No to remove a panel event
7. Choose Save.
Programming in-suite signal silence
In-suite signal silence is programmed using two separate menus:
Configure the elapse timer for in-suite signal silence by displaying the Program > Advanced
Program > Panel Operation menu.
The function is enabled for individual correlation groups through the Program > Advanced
Program > Loop Configuration > Correlation Groups menu.
This section provides instructions for setting both in-suite signal silence options.
Note: When setting up correlation groups for in-suite signal silence, the group’s activation
count must be set to 1. See “Setting a correlation group’s activation counton page 85.