9.4.4 Set the airflow coefficient (CP210-R)
This function is available on CP210-R with SQR3 option only.
This coefficient allows to calculate an airflow from the pressure. It is indicated by the manufacturer that supplies air vents
with pressure connections (+ and -). From the square root of the measured pressure (Delta P), and this coefficient, you will
get the airflow:
Airflow=C
D
Δ pressure
The transmitter is powered on.
Press OK.
Enter the activation code (see page 8).
Press OK.
Press Up key to go to “F 625” folder to set the coefficient value.
Press OK.
Set the coefficient with Up and Down keys.
Press OK when the last digit has been set to validate the coefficient.
This coefficient must be between 0000.0 and 9999.9.
Press Up key to go to “F 626” folder to set the unit of measurement.
Press OK.
Select 0, 1, 2, 3 or 4 for:
0: Pa
1: mmH
2
O
2: inWG
3: mbar
4: mmHG
24
F 600: COMPENSATION, MEANS OF MEASUREMENT AND SECTION SETTINGS