9.4.4 Set the airflow coefficient (CP210-R)
This function is available on CP210-R with SQR3 option only.
This coefficient allows to calculate an airflow from the pressure. It is indicated by the manufacturer that supplies air vents
with pressure connections (+ and -). From the square root of the measured pressure (Delta P), and this coefficient, you will
get the airflow:
The transmitter is powered on.
➢ Press OK.
➢ Enter the activation code (see page 8).
➢ Press OK.
➢ Press Up key to go to “F 625” folder to set the coefficient value.
➢ Press OK.
➢ Set the coefficient with Up and Down keys.
➢ Press OK when the last digit has been set to validate the coefficient.
This coefficient must be between 0000.0 and 9999.9.
➢ Press Up key to go to “F 626” folder to set the unit of measurement.
➢ Press OK.
➢ Select 0, 1, 2, 3 or 4 for:
➢ 0: Pa
➢ 1: mmH
2
O
➢ 2: inWG
➢ 3: mbar
➢ 4: mmHG
24
F 600: COMPENSATION, MEANS OF MEASUREMENT AND SECTION SETTINGS