3.8. Recommended Log Format for KAC Units
Leaving evaporator liquid
temperature
Saturated suction pressure
Saturated suction
temperature
Suction Superheat,
(difference of Sr. 10 & 11)
Number of fans ON at the
time of log (air-cooled units)
Saturated discharge pressure
Saturated discharge
temperature
Discharge line temperature
NOTE:
a) This is a sample recommended log sheet format given only for guidance. Customer shall have
a detailed log than the sample shown here.
b) Operational data of the unit shall be recorded for minimum interval of two hours of operation.
NOTE: CRANKCASE HEATERS SHOULD BE OPERATED AT
LEAST 24 HOURS PRIOR TO START- UP. CRANKCASE SHOULD
BE WARM. OPEN ALL THE CLOSED VALVES BEFORE
STARTING.