KIRLOSKAR CHILLERS PRIVATE LIMITED
A Kirloskar Group Company IOM-KAC-ENG - Page 44
Now it will follow schedule of each weekdays but on specified holidays it will follow schedule
mentioned for holiday).
4) Alarm History :- Logging of last 99 alarms with 4 Variables (critical parameters) which
can be viewed with display
5) RTC based Anti-recycle time (Start to Start / Stop to Start).
6) Starting / Stopping on Chilled Water Outlet is automatic.
7) PC-Connectivity is possible (separate software/hardware to be procured for this).
8) Important variables list incorporated for getting connected to BMS system
6.2.2. Connector Details:
1. Power supply connector [G (+), G0 (-)];
2. Yellow power LED and 3 status LEDs
3. Additional power supply for the terminal and 0 to 5 V ratio metric probes;
4. Universal analogue inputs: NTC, 0 to 1 V, 0 to 5 V ratio metric, 0 to 10 V, 0 to 20 mA, 4 to 20
mA;
5. Passive analogue inputs: NTC, PT1000, ON/OFF;
6. 0 to 10 V analogue outputs;
7. 24 VAC/VDC digital inputs;
8. 230 VAC or 24 VAC / VDC digital inputs;
9. Connector for the display panel (external panel with direct signals);
10. Connector for all standard PCO series terminals and for downloading the application
program;
11. Relay digital outputs;
12. Connector for connection to the I/O expansion board;
13. PLAN network connector;
14. Cover for inserting the supervisor (Modbus) card option