3.7 Crankcase Ventilation (CCV) Heater Kit GM78171-KP1
Applies to 125/150 kW, 8.1 L GM-powered and 8.8 L PSI-powered generator set models. Consult your local generator set
distributor/dealer for additional information.
The crankcase ventilation (CCV) heater kit provides a controlled heating source to the crankcase ventilation system preventing
freezing water buildup during cold weather. The thermostat turns on at 4°C (40°F) and turns off at 16°C (60°F) reducing energy
consumption. See Figure 46.
Figure 46 Crankcase Ventilation Heater Kit
3.8 Air Cleaner Restrictor Indicator (if equipped)
The air cleaner restriction gauge mounted on the air cleaner(s) helps determine the air cleaner change interval.
The air cleaner restriction gauge monitors air flow and continuously displays restriction readings indicated as vacuum
(see Figure 47). Increased restriction indicates a clogged air cleaner element.
As maximum allowable restriction is reached, the gauge window turns red indicating the air cleaner element needs replacement.
To reset the gauge, push the gauge top down and release.
Figure 47 Restriction Indicators (styles vary)
Heater element
Inline connector
Thermostat
AC power cord
Push down to reset
Display
Gauge window
273113

Table of Contents

Other manuals for Kohler Decision-Maker 3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Decision-Maker 3000 and is the answer not in the manual?

Kohler Decision-Maker 3000 Specifications

General IconGeneral
BrandKohler
ModelDecision-Maker 3000
CategoryController
LanguageEnglish

Related product manuals