TP-6694 9/20 81
SystemComponent
Action
Interval
Visually Inspect
Check
Change
Clean
Test
AC Electrical System
Controller lamp test
X
R
Weekly
General Inspection
X
Weekly
Circuit breakers, fuses†
X
X
R
X
X
Monthly
Wire abrasions where subject to motion
X
X
Quarterly
Safety and alarm operation
X
X
Six Months
Tighten control and power wiring
connections
X
Yearly
Transfer switch main contacts†
X
X
Yearly
Voltage-sensing device/relay adjustment†
Yearly
Wire-cable insulation breakdown
X
X
3 Years or 500 Hrs.
Engine and Mounting
General inspection
Weekly
Governor operation, lubricate moving parts
Refer to engine operation
manual for service intervals
and instructions.
Air cleaner service
Choke, carburetor adjustment
Governor oil (mechanical governor only)
Ignition components
Injector pump and injector flow rate,
pressure, spray pattern
Valve clearance
Bolt torque
Remote Control System, etc.
Compartment condition
X
X
Weekly
Remote control
X
Monthly
Run generator set
X
Monthly
Alternator
General inspection
X
Weekly
Rotor and stator
X
X
Yearly
Bearing condition
X
X
R
Yearly
Exciter
X
X
X
Yearly
Voltage regulator
X
X
X
Yearly
Measure and record resistance readings of
windings with insulation tester (Megger
®
,
with SCR assembly or rectifier
disconnected)
X
Yearly
Blow dust out of alternator*
X
2 Years or 300 Hrs.
General Condition of Equipment
Any condition of vibration, leakage, noise,
temperature, or deterioration
X
X
X
Weekly
Ensure that system is set for automatic
operation
X
Weekly
Interior of equipment room or outdoor
weather housing
X
X
Weekly
● Follow procedures and frequencies indicated in the engine manufacturer’s maintenance manual.
If not indicated, follow this service schedule. Some items may not apply to all generator sets.
R Replace as necessary.
X Action
* Service more frequently if operated in dusty areas.
† Do not break manufacturer’s seals or internally inspect these devices.
Megger
®
is a registered trademark of Biddle Instruments.

Table of Contents

Other manuals for Kohler Decision-Maker 3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Decision-Maker 3000 and is the answer not in the manual?

Kohler Decision-Maker 3000 Specifications

General IconGeneral
BrandKohler
ModelDecision-Maker 3000
CategoryController
LanguageEnglish

Related product manuals