Err_5: LOAD SENSOR CALIBRATION ERROR - The no-load (SL 0) setting voltage is out of
range.
Normal action: Repeat the setup routine. Measure the voltage between CU1:2
and CU1:3 (values should be found somewhere in the range of 3,9 - 6,1 VDC with
any load from 0 to 100 %).
Err_6: LOAD SENSOR CALIBRATION ERROR - The full-load (SL100) setting voltage is out of
range.
Normal action: The same action as with the Err_5.
Err_7: LOAD SENSOR CALIBRATION ERROR - The voltage difference between the no-load
(SL 00) and full-load (SL100) setting voltages is too low.
Normal action: Repeat the setup routine. If the error still occurs check the load
sensor and its mounting. The voltage difference measured between CU1:2 and
CU1:3 must be at least 0,4 VDC between the no-load and full-load settings.
Err_8: MEMORY ERROR, UPDATE - the CU1 has failed to update its memory content.
Normal action: Switch the power off for at least 5 seconds. If this does not help,
change the CU1.
Err_9: SYSTEM ERROR (≥ P2.02)
Normal action: Switch the power off for at least 5 seconds. If this does not help,
change the CU1.
Err_10: CU1:9-10 CHECKING FAILURE (≥ P2.11) - The CU1 has detected a continuous
hoisting request in non-active state (active signal, CU1:13-CU1:14, is OFF but hoisting
request is ON) - i.e. this error message is displayed if the hoisting request is not
requested by a crane operator or the hoisting direction is changed very rapidly from
downwards to upwards. (CU1 checks that the hoist inhibit switch between CU1:9 and
CU1:10 operates correctly).
Normal action: Check hoisting request circuit that the hoisting request is OFF
when it should be. If there is voltage on CU1:9 (> 30 VAC) without a hoisting
request, check the hoisting control circuit.
The Err_10 may also be caused because of very long control wires i.e.
capacitance on wires is too large. In that case connect a RC-circuit between
CU1:9 and control voltage neutral (e.g A-K1:A1). If this does not help replace the
CU1.
Err_11: TOO LONG AD-CONVERSION TIME (≥ P2.13) - CU1 detects, that the AD-
conversion time is too long when power is switched on.