26.03.1996 • KHH SEENXL13A
•For Authorized KCI Service Agents Only•
KCI Hoists Corporation reserves the right to alter or amend the above information without notice
Page 17
XL
Service Manual
CU1
KCI KONECRANES GROUP
KCI HOISTS CORPORATION
5 SETUP ROUTINE
Before carrying out the setup routine make it clear to yourself what is the difference
between the setup and startup routines.
During the setup routine one sets the hoist class and calibrates the load sensor (a test
load is needed during the setup routine).
Note: The setup routine is normally carried out at the hoist factory on all new hoists and
thus, normally, it is not necessary to carry out the setup routine again.
Note:
Read through the whole setup routine instruction and make sure that you
Read through the whole setup routine instruction and make sure that youRead through the whole setup routine instruction and make sure that you
Read through the whole setup routine instruction and make sure that you
are familiar with all steps and effects of the
are familiar with all steps and effects of the are familiar with all steps and effects of the
are familiar with all steps and effects of the setup routine
setup routinesetup routine
setup routine before you start.
before you start. before you start.
before you start.
Lifting of the test load is permitted in step 3 only.
1 Change the CU1 into the programming and controlling mode
a) Change the CU1 to the beginning of the programming and controlling mode
by pressing the blue push-button until the 'PAUSE'-message appears. Release the
push-button.
b) Change the CU1 into the programming and controlling mode by entering
value 1-630 at password_1.
2 Change the CU1 into the setup mode by selecting the procedure in calibrating
the load sensor (calibration with a load as close to the rated load of the hoist as
possible is always recommended, i.e. procedure 1 or 3):
There are four ways to calibrate the load sensor according to the weight of the test
load. Procedure is selected by password_2:
Proc. 1: 2-611 Calibration with the rated load of the hoist (100%).
Proc. 2: 2-622 Calibration with a known load, 50...99 % of the hoist's rated
load. This is allowed only in cases that the rated load of the hoist is not available.
However, if there is an overload device with so called 'plate springs', the load
sensor should always be calibrated with the rated load (or 110 %) in order to
achieve the required accuracy at a 110 % load. (Normally, XL100-XL400 hoists
on LA-trolleys are equipped with a 'plate spring' overload device.)
CU1 is a safety device. Programming is allowed by specially trained people only.
CU1 is a safety device. Programming is allowed by specially trained people only.CU1 is a safety device. Programming is allowed by specially trained people only.
CU1 is a safety device. Programming is allowed by specially trained people only.
If necessary, please contact the KCI Konecranes Service organization.
If necessary, please contact the KCI Konecranes Service organization.If necessary, please contact the KCI Konecranes Service organization.
If necessary, please contact the KCI Konecranes Service organization.