22
6.5 HEATING LOOPS WITH THE KT1 OR KT2A THERMOSTATS MENU
N
During the commisioning protocol set one KT–1 or KT–2A for each heating loop.
Heating loop
Menu
Parameter name Parameter value range Note
Heating loop
operational
mode
ON – Turn on
AUTO – Working schedule
OFF – Turn off
Desired
ambient
temperature
+17 °C/+27 °C
Set the desired ambient temperature on which basis
the KSM regulator calculates the right water tempe-
rature in the heating loop.
ECO ambient
mode
–10 °C/0 °C
ECO lowering the ambient temperature by the set
value.
COMFORT
ambient mode
0 °C/+10 °C
COMFORT raising the ambient temperature by the
set value.
Setting the
schedule
1–7 days
0 − 24 h
Weekly operational schedule.
Weather mode
−15 0C
This is set only if adaptive
regulation is turned off.
The value depends on the
setting at commissioning.
See chapter 6.8
Heating curve setting at –15 °C ambient temperature.
Weather mode
+15 0C
This is set only if adaptive
regulation is turned off.
The value depends on the
setting at commissioning
Heating curve setting at +15 °C ambient temperature.
N
If adaptive regulation is turned off, the KSM regulator calculates the temperature of the water in the heating
loop based on the heating curve with reference temperatures at −15 °C and +15 °C.
For a constant water temperature in the heating system set the setting at –15 °C and at +15 °C to the same value.
Operating instructions
ADAPT, VERSI, ETERA and WPLV systems
17-19-45-6702-07