6.6 MENU HEATING LOOPS WITHOUT THE KT1 OR KT2A THERMOSTATS MENU
Heating loop
Menu
Parameter name Parameter value range Note
Heating loop
operational
mode
ON – Turn on
AUTO – Working schedule
OFF – Turn off
ECO loop mode –10 °C/0 °C
ECO lowering the temperature of the heating loop by
the set value.
COMFORT loop
mode
0 °C /+10 °C
COMFORT raising the temperature of the heating
loop by the set value.
Setting the
schedule
1–7 days
0–24 h
See chapter 6.8
Weekly operational schedule.
Weather mode
−15 C
The value depends on the
setting at commissioning or
user settings.
Heating curve setting at –15 °C ambient temperature.
Weather mode
+15 C
The value depends on the
setting at commissioning or
user settings.
Heating curve setting at +15 °C ambient temperature.
N
If there is no KT–1/KT–2A thermostat, adaptive regulation is turned off. The KSM regulator calculates the
temperature of the water in the heating loop based on the heating curve with reference temperatures at −15 °C
and +15 °C.
For a constant water temperature in the heating system set the setting at –15 °C and at +15 °C to the same value.
Operating instructions
ADAPT, VERSI, ETERA and WPLV systems