User Manual User Manual
49
50
Enable
Or, if enabled, to set the
export power limit.
Power
DRM
Enable
Disable
Disable
Enable
EPS
Enable
Disable
Enable
Enable
Remote
CTRL
Disable
Disable
Enable
Start
Delay
20…300Seconds
30Seconds
CEI SPI
Ctrl
Disable
Disable
Enable
Disable
Enable
Enable
DOD
Enable
Disable
Enable
Enable
Generator
Disable
Disable
Enable
CT or
METER
CT
CT
Meter
AC
Couple
Disable
Disable
Enable
BAT
Setting
BAT
Type
Lead-
Acid
FLOAT-
VOLT
LFP
EQCHAR
VOLT
BAT CAP
BAT OVP
LFP
DISC
Depth
10%~90%
90%
OFFGRID
DOD
0%~100%
95%
CHG
CURR
1~160A
160A
DISC
Power
0%~100%
100%
CHG
Power
1%~100%
100%
BAT End
Volt
40~48V
43.2V
BAT
Wake-up
Enable Disable
Enable
If Enable is selected, the user
will be prompted to enter the
power.
Only applicable in Austrailia
and New Zealand at this time.
Enables the Backup output
(the Load Switch needs to be
turned ON).
Allows control via RS485
(Scada system for example).
This is the boot delay from
when power is applied to the
inverter.
This function is only
applicable to use via DRM for
remote control (Australian
and New zealand markets
only).
Ground fault monitoring on
the AC grid connection.
Depth of discharge. This
should always be enabled.
Disabling will result in the
battery discharging to 0%.
This option allows the user to
install a secondary means of
generation. For example,
wind generator or diesel
generator.
CT option is used for
measuring the system current.
Meter option is used for
measuring the system current.
Allows the user to connect an
external inverter to the system
(either instead of PV, or in-
addition to PC - Hybrid mode).
Select the battery type.
Sets the maximum depth of
discharge during grid
connected state.
Sets the maximum depth of
discharge when off-grid.
Sets the maximum battery
charge current.
Sets the maximum discharge
power - % of rated output.
Sets the maximum charge
power - % of rated output.
Sets the voltage that is seen
as 0% remaining.
If enabled the battery will
contantly monitor state of
charge and depth of discharge.
If time option is selected, the
battery will wake up and check
set the
export power
limit(Range:
0~rated
power)
GFCICHK
ENB
Menu
Level 1
Menu
Level 2
Menu
Level 3
Menu
Level 4
Menu
Level 5
Menu
Level 6
Default
Selection
Comment
Menu
Level 1
Menu
Level 2
Menu
Level 3
Menu
Level 4
Menu
Level 5
Menu
Level 6
Default
Selection
Comment