Single Battery Capability: Must modify the value to actual configuration, The value can
be 7~2000.
Boost/Float conversion: boost charge and float charge alternate time, The value can
be 0~20.
Chg.cur.limiting coef.: The charging current limit is a multiple of the battery capacity.
The value can be 0.05~0.15, and is 0.1 by default.
Cell float voltage: The float voltage value can be 2.23~2.30 V/cell, and is 2.25 V/cell by
default.
Cell boost voltage: The battery equalized voltage value can be 2.30~2.40 V/cell, and is
2.30 V/cell by default.
Aver charging Duration: boost charge time limit, the value can be 1~999min , and is
240 by default.
EOD Battery Volt: End of discharge voltage. The value can be 1.60~1.90, and is 1.80 by
default.