53
Float Temp Compen Coeff: modify the voltage of compensation after enable theswtich.
the value can be 0.001~0.007/cell, and is 0.003 by default.
Boost Charge Setting: Boost charge disable or enable, and is enable by default.
No Battery Warning: can be no warning when no batter after set disable, and is enable
by default.
Cabinet shared battery: tow parallel ups use common batter bank. The value can be
set share battery pack or Not shared battery P, not shared battery P by default.
Generator on prohibit charging: UPS disable charge the battery if set the value to
enable when the generator signal is enable.
Bypass Volt Prot Lower Limit: When the difference between the bypass voltage and
the rated voltage exceeds the lower threshold for the
bypass voltage, the system determines that the bypass
voltage is abnormal and that the bypass is unavailable.
The value can be -10%, -15%, -20%, -30%, -45%,. The