71
Current THDi ≤3%(100% nonlinear load)
Bypass Voltage
Range
Max.voltage: 220V:+25 %( optional +10%, +15%, +20%);
230V:+20 %( optional +10%, +15%);
240V:+15 %( optional +10%);
Min. voltage:-45 %( optional -10%, -20%,-30%)
Frequency protection range: ±10%
Output
Phase 3 Phase 4 Wires and Ground
Rated Voltage 380/400/415Vac
Power Factor 1
Voltage Regulation ±1%
Frequency
Utility
Mode
±1%/±2%/±4%/±5%/±10%of the rated frequency(optional)
Battery
Mode
(50/60±0.1)Hz
Crest Factor 3:1
THD
≤2% with linear load
≤4% with non linear load
Overload
Inverter overload capability:
◆ 105% < load ≤ 110%: transfer to bypass mode after 60
min
◆ 110% < load ≤ 125%: transfer to bypass mode after 60
min
◆ 125% < load ≤ 150%: transfer to bypass mode after 60
min
Bypass overload capability:
◆ Temperature ≤ 30°C, load ≤ 135%: run for a long time
◆ Temperature ≤ 40°C, load ≤ 125%: run for a long time
◆ 1000% load: run for 100 ms
Battery
Voltage
Optional Voltage:
±180V/192V/±204V/±216V/±228V/±240/±252/±264/±276/±
288/±300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs
optional)
360Vdc~600Vdc (30~50 pcs, 36 pcs define, 36 ~ 50 pcs
no power derating; 32~34 pcs output power factor 0.9;30
pcs output power factor 0.8;)
charge current (A) max. 140A 180A 200A
Transfer Time Utility to Battery : 0ms; Utility to bypass: 0ms
Protection
Short Circuit Hold Whole System
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down
UPS immediately
Battery Low Alarm and Switch off
Self-diagnostics Upon Power On and Software Control
EPO Shut down UPS immediately
Battery Advanced Battery Management
Noise Suppression Complies with EN62040-2
Communication Interface
CAN, RS232, RS485, LBS, Parallel, Relay card, SNMP
card(optional)
Environment
Operating
Temperature
0℃~40℃
Storage Temperature
-25℃~55℃
Humidity
0~95% non condensing