72
Altitude < 1500m
Display
Audible & Visual Line Failure, Battery Low, Overload, System Fault
Status LED UPS Fault, Alarm and normal
Reading On the LCD
Input Voltage, Input Frequency, Output Voltage, Output
Frequency, Load Percentage, Battery Voltage, parameter
set, history record…
Other
Standard cabinet
Dimensions(W*D*H)
600*850*2000
1200*850*2000
Full cabinet
Dimensions(W*D*H)
(mm)
Safety Conformance CE,EN/IEC 62040-3,EN/IEC 62040-1-1
Model
800kVA 1000kVA 1200kVA
Cabinet capacity (VA/W)
400k / 400k 500k / 500k 600k / 600k
Input
Phase 3 Phase 4 Wires and Ground
Rated Voltage 380/400/415Vac
Voltage Range
138~485Vac
◆ At 40°C: The UPS works at full load when the voltage is
323–485Vac and is derated load when the
voltage is 323–138Vac
◆ At 30°C: The UPS works at full load when the voltage is
305–485Vac and is derated load when the
voltage is 305–138Vac
Frequency Range 40Hz-70Hz
Power Factor ≥0.99
Current THDi ≤3%(100% nonlinear load)
Bypass Voltage
Range
Max.voltage: 220V:+25 %( optional +10%, +15%, +20%);
230V:+20 %( optional +10%, +15%);
240V:+15 %( optional +10%);
Min. voltage:-45 %( optional -10%, -20%,-30%)
Frequency protection range: ±10%
Output
Phase 3 Phase 4 Wires and Ground
Rated Voltage 380/400/415Vac
Power Factor 1
Voltage Regulation ±1%
Frequency
Utility
Mode
±1%/±2%/±4%/±5%/±10%of the rated frequency(optional)
Battery
Mode
(50/60±0.1)Hz
Crest Factor 3:1
THD
≤2% with linear load
≤4% with non linear load
Overload
Inverter overload capability:
◆ 105% < load ≤ 110%: transfer to bypass mode after 60
min
◆ 110% < load ≤ 125%: transfer to bypass mode after 60
min
◆ 125% < load ≤ 150%: transfer to bypass mode after 60