EasyManua.ls Logo

KYORITSU 6050 - RCD Testing

KYORITSU 6050
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
6.2RCDTesting
6.2.1Preparation
(1)TurnFunctionswitchandpowerontheinstrument.SelectRCD.
(2)PressRCDFunctionswitchtoselectRCDFunctionfortest.
SelectedfunctionwillbedisplayedonLCD.
(3)Pressthe"I⊿n/LOOP/PSC"SELECTSWITCHtosettheRated
TrippingCurrent (I⊿n) to the rated trip current of the RCD. Every
time"I⊿n/LOOP/PSC"SELECTSWITCHispressed,▼markon
LCDshifts.SelectI⊿nwithaboveswitch.
(4)Pressthe UL value select switch to select switch ULvalue (25 or
50V).
6.2.2WiringCheck
(1)InserttheTestLeadintotheinstrument.(Fig.15)
(2)Connecttestleadtoobjecttobetested.(Fig.16,17)
(3)MakesurethattheP-EandP-NwiringCheckLEDsarelitandthe
wiringincorrectLED is notlit.Ifitisnotcorrect,disconnectthe
testerandcheckthewiringforapossiblefault.
FortestingRCD'stoverifythat
theyarenottoosensitive.
Formeasuringthetriptime.
FortestingatI⊿n×5.
FortestingDCsensitiveRCD's.
Formeasuringthetripoutcurrent.
×1/2
×1
×5
DC
AUTORAMPTEST( )
RCDFunction
I⊿n
0°/180°
UL
×1/2
30mA
50V
TheInitialvalue

Related product manuals