7
datatoPC"
forfurtherdetails.
Windows
R
isaregisteredtrademarkofMicrosoftintheUnitedstates.
3.4TestRange(Function)
Model6050performsfourfunctions.
1.LOOP.....Loopimpedancetester
2.RCD.......RCDtester
3.Uc..........Contactvoltagetester
4.PSC........Prospectiveshortcircuitcurrenttester
3.5AppliedStandards
Instrumentoperation:IEC/EN61557-1,3,6,10
Safety: IEC/EN61010-1CATⅢ(300V)-instrument
IEC/EN61010-2-031CATⅢ(600V)-testlead
Protectiondegree: IEC60529(IP54)
3.6Features
Model6050hasthefollowingfeatures:
Wiringcheck
ThreeLEDsindicateifthewiringofthecircuit
undertestiscorrect.
Overtemperature
protection
Detectsoverheatingoftheinternalresistorand
ofthecurrentcontrolMOSFETdisplayinga
warningsymbol( )andautomaticallyhalting
furthermeasurements.
Phaseangle
selector
RCDtestcanbeselectedfromeitherthe
positive(0°)orfromthenegative(180°)half-
cycleofvoltage.Atbothpolarity,testminimum
(best)andmaximum(worst)triptimes.
Autodatahold
Measuredresultisbeinghelduntilanyswitch
otherthanMEMswitchispressed.Instrument
isbacktovoltagemeasurementmodewhen
applyingvoltageagainduringdatahold
functionisoperated.