12) COMMISSIONING OF AUTOMATIC DOOR (INITIAL SET-UP)
After performing the mechanical installation of the automatic door and the electrical connections to
the electronic control unit, make the automation set-up.
• Preliminary checks:
- check the cleanliness of the sliding rail and of the ground guide;
- check the belt’s tension;
- check that leaves are properly aligned and fastened to the carriages;
- check that the position of the mechanical limit switch is correct;
- check that leaves move smoothly and frictionless;
- check proper operation of the electric lock, if installed, and of the relevant manual release.
SET-UP operation is necessary to allow the operator electronic control unit to acquire stroke end
points.
During the stroke learning cycle there must be no obstacles in the leaf movement area.
• SET-UP
BEFORE STARTING THE SET-UP MOVE THE DOOR TO THE CLOSING POSITION.
THE AUTOMATION WILL DETECT AUTOMATICALLY THE CORRECT DIRECTION OF
OPENING DURING THE SET-UP CYCLE.
Strictly follow the next steps:
a) Set automation type by dip 1 of S1:
OFF = Eterna Easy 150
ON = Eterna Easy 90
b) Set electric lock type by dip 2 of S1:
OFF = ET-FSE (fail secure)
ON = ET-FSA (fail safe)
c) Supply power to the electronic control unit, the buzzer will emit 5 short beeps.
d) Press and hold the "PS1 SET-UP" black button as long as the control unit buzzer emits
the long beep, then release it when the control unit emits the 4 final beeps preceding motor
starting.
e) The door starts closing fully, then it performs an opening cycle at slow speed, which must be
necessarily completed.
At the end of the cycle a prolonged BEEP stands for the set-up completed.
After a few seconds the door closes automatically.
NOTE: In case it is necessary to interrupt the execution of the set-up cycle, press the
PS2-START button.
At the end of the set-up, set the functions of the dip-switches S1, S2, S3 and potentiometers
on the control unit ET-LOGIC EASY reading carefully the next paragraph “Functions and
potentiometers”.
25
PS1