EasyManua.ls Logo

Lamtec BurnerTronic BT340 - Technical Data; Technical Data BT300

Lamtec BurnerTronic BT340
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
41
7 Technical Data
7 Technical Data
7.1 Technical Data BT300
Function
Power supply: 230 V +10/-15 % 47-63 Hz
115 V +10/-15 % 47-63 Hz (on request)
Maximum backup-fuse: 10 A slow-blow
To be used only in a grounded power line network!
Power consumption: max. 30 VA
Switching threshold of ionisation
current:
1 A
Digital signal inputs: Max. line length 10 m
Digital outputs: 3 fuel valves max. 1 A cos 0,4
VL fan max. 2 A cos 0,4
oil pump max. 2 A cos 0,4
ignition transformer max. 2 A cos 0,2
alarm output max. 1 A cos 0,3
Resolution: 999 digit, 10 bit
Number of curve sets: BT320/33x: 1 curve set (oil or gas)
BT34x: 2 curve sets (oil/gas switchable; DFM300 or LCM100 required)
Number of programs: unlimited (EEPROM)
Field bus-coupling (optional): PROFIBUS
LCM100 always required
Housing: Polycarbonate + ABS
Dimensions: 200x115x61 mm
Weight: 1,0 kg
Flammability: UL-94 V0 (panel: UL-94 V2)
Display
Display: 128x64 pixel, monochrome
White backlighting (dimmable)
Dimensions: 112 x 64 x 24 mm
Weight: 140 g
Housing: Basic housing: Polyamide glass fibre reinforced
LCD-display window: Polycarbonate
Flammability: Basic housing UL-94 V0
LCD-display window UL-94 V2
Environmental Conditions
Operation: Climatic conditions Class 3K5 according to DIN EN 60721-3
Mechanic conditions Class 3M5 according to DIN EN 60721-3
Temperature range -20 ... +60 °C (condensation is prohibited)
Transport: Climatic conditions Class 2K3 according to DIN EN 60721-3
Mechanic conditions Class 2M2 according to DIN EN 60721-3
Temperature range -20 ... +70 °C (condensation is prohibited)