30
7 Operation
7 Operation
7.1 Operation/Measurement Value Display
Display and operating unit (optional) is included as a
standard in LT2 19” for panel installation.
Service and diagnostic software (optional)
Limited by multifunction key and monitor output
7.1.1 Measurement Value
•O
2
actual value 0 30 % vol O
2
Resolution: 0.1 % vol O
2
up to 18 % vol O
2
1.0 % vol O
2
above 18 % vol O
2
Probe voltage -30 ... +150 mV
Resolution: 0.1 mV
AC internal resistance of the ZrO
2
cell 0 750
Resolution: better than 0.2
Displayed up to 999.9
Exhaust gas temperature (optional) 0 320 °C/32 °F ... 608 °F
Resolution:
Alternatively:
Resolution:
1 °C/33.8 °F
0 ... 850 °C/
32 °F ... 1562 °F
better than 2 °C/
35.6 °F
Combustion efficiency (optional) 0 100 %
Resolution:
0.1 %
Calculated CO
2
-concentration (optional) 0 20 % vol
Resolution:
0.1 % vol
CO/H
2
concentration, shown as
CO
e
[CO
equivalent
]
0 10,000 ppm
Resolution:
Alternatively:
variable 1 ... 100 ppm
depending on meas-
ured value
1 % of measured
value,
not better than 1 ppm
Customised values Can be freely configured, e.g. exhaust
gas, temperature, efficiency, CO
2
con-
centration etc.

Table of Contents