CS-D1008E Closed Loop Stepper Drive User Manual
Page | 12
8. Sequence Chart of Control Signals
In order to avoid some fault operations and deviations, PUL, DIR and ENA should abide by some rules, shown as
following diagram:
Figure 8: Sequence chart of control signals
Remark:
(1) t1: ENA must be ahead of DIR by at least 500ms. Usually, ENA+ and ENA- are NC (no connected). See
“Connector P1 Configurations” for more information.
(2) t2: DIR must be ahead of PUL effective edge by 5us to ensure correct direction.
(3) t3: Pulse width not less than 1us @ 5V, 2.5us @ 24V, these widths are based on a 50% duty cycle. If it is
greater or less than 50%, the width time is required to be wider.
9. Fault Protections
To improve reliability, the drive incorporates some built-in protection features.
Turn off the power immediately.
a) Check wiring is short-circuited or not;
b) Check motor is short-circuited or not.
Turn off the power immediately.
a) Check if the power voltage is higher
than 160VDC
Restart the power supply, if the drive is
still alarm, please contact after-sale
a) The drive is not connected to a motor.
b) If alarm is occurred when connect a
motor, please check the motor wiring.