Besuretocheckforgasleaks.
12.6. Servicing Indoor Unit Refrigeration
Circuit
12.6.1. Collecting Refrigerant into Outdoor Unit
Conrmthatboththetwo-wayandthree-wayvalves
aresettotheopenedposition
Removethevalvestemcapsandconrmthatthevalve
stemsareintheopenedposition.
Besuretouseahexagonalwrenchtooperatethe
valvestems.
Connectthechargehosewiththepushpinofhandlelo
tothethree-wayvalvesgasserviceport.
Airpurgingofthechargehose-OpenthehandleLo
valveofthemanifoldvalveslightlytopurgeairfromthe
chargehoseforvesecondsandthencloseitquickly.
Setthetwo-wayvalvetothecloseposition.
Operatetheairconditioneratthecoolingcycleand
stopitwhenthegaugeindicates0.1MPa(14psi).
Setthethree-wayvalvetotheclosedposition
immediately
Dothisquicklysothatthegaugeendsupindicating0.3
to0.5Mpa(43-72psi).
Disconnectthechargeset,andtightenthetwo-way
andthree-wayvalve’sstemnuts.
Useatorquewrenchtotightenthethree-wayvalves
serviceportcaptoatorqueof18N.m.
Besuretocheckforgasleakage.
12.6.2. Air Purging with Vacuum Pump
Completelytightenthearenutsoftheindoorand
outdoorunits,conrmthatboththetwo-wayandthree-
wayvalvesaresettotheclosedposition.
Connectthechargehosewiththepushpinofhandlelo
tothethree-wayvalvesgasserviceport.
Connectthechargehoseofhandlehiconnectiontothe
vacuumpump.
FullyopenthehandleLoofthemanifoldvalve.
Operatethevacuumpumptoevacuate.
Makeevacuationfor30minutesandcheckwhetherthe
compoundmeterindicates-0.1Mpa(500microns).If
themeterdoesnotindicate-0.1Mpa(500microbars)
afterpumping30minutes,itshouldbepumped20
minutesmore.Ifthepressurecan’tachieve-0.1Mpa
(500microbars)afterpumping50minutes,please
checkiftherearesomeleakagepoints.
FullyclosethehandleLovalveofthemanifoldvalve
andstoptheoperationofthevacuumpump.Conrm
thatthegaugeneedledoesnotmove(approximately
veminutesafterturningoffthevacuumpump).
Turnthearenutofthethree-wayvalvesabout45°
counterclockwiseforsixorsevensecondsafterthegas
comingout,thentightenthearenutagain.Makesure
thepressuredisplayinthepressureindicatorisalittle
higherthantheatmospherepressure.Thenremovethe
chargehosefromthethree-wayvalve.
Fullyopenthetwo-wayvalveandthree-wayvalveand
securelytightenthecapofthethree-way
12.7. Evacuation after Servicing the Outdoor
Unit Refrigeration Circuit
12.7.1. Evacuation of the Complete Refrigeration
Circuit, Indoor and Outdoor Unit
Conrmthatboththetwo-wayandthree-wayvalves
aresettotheopenedposition.
Connectthevacuumpumptothree-wayvalve’sservice
port.
Evacuationforapproximatelyonehour.Conrmthat
thecompoundmeterindicates-0.1Mpa(500Microns/
29.9in.hg).
Closethevalve(Lowside)onthechargeset,turnoff
thevacuumpump,andconrmthatthegaugeneedle
doesnotmove(approximately5minutesafterturning
offthevacuumpump).
Disconnectthechargehosefromthevacuumpump.
12.7.2. Refrigerant Charging
Connectthechargehosetothechargingcylinder,open
thetwo-wayvalveandthethree-wayvalve.
Connectthechargehosewhichyoudisconnectedfrom
thevacuumpumptothevalveatthebottomofthe
cylinder.IftherefrigerantisR-410A,makethecylinder
bottomuptoensureliquidcharge.
Purgetheairfromthechargehose
Openthevalveatthebottomofthecylinderandpress
thecheckvalveonthechargesettopurgetheair(be
carefuloftheliquidrefrigerant).
Putthechargingcylinderontotheelectronicscaleand
recordtheweight.
Openthevalves(Lowside)onthechargesetand
chargethesystemwithliquidrefrigerant.Ifthe
systemcannotbechargewiththespeciedamount
ofrefrigerant,orcanbechargedwithalittleatatime
(approximately150geachtime),operatingtheair
conditionerinthecoolingcycle;however,onetimeis
notsufcient,waitapproximately1minuteandthen
repeattheprocedure.
Whentheelectronicscaledisplaystheproperweight,
disconnectthechargehosefromthe3-wayvalve’s
serviceportimmediately
Ifthesystemhasbeenchargedwithliquidrefrigerant

Table of Contents

Other manuals for Lennox MHA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MHA Series and is the answer not in the manual?

Lennox MHA Series Specifications

General IconGeneral
BrandLennox
ModelMHA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals