Commissioning
The most important codes for commissioning
EDK82MV222 DE/EN/FR 9.0
L
NOS
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0013
uSEr
Deceleration
time main
setpoint
5.00 0.00 {0.02
s}
1300.00 Reference: frequency change
C0011 ... 0 Hz
z Additional setpoint Ö
C0221
z Deceleration times can be
activated via digital
signals
Ö C0103
C0014
Operating
mode
2
2 V/f characteristic control V ~ f
(Linear characteristic with constant
V
min
boost)
z Commissioning without
motor parameter
identification possible
z Benefit of identification
with C0148:
– Improved smooth
running at low speed
– V/ f rated frequency
(C0015) and slip
(C0021) are calculated
and stored. They do not
have to be entered
3 V/f characteristic control V ~ f
2
(Square-law characteristic with
constant V
min
boost)
4 Vector control
For initial selection enter
the motor data and identify
the motor parameters with
C0148
Otherwise commissioning
is not possible
5 Sensorless torque control with
speed limitation
z Torque setpoint via C0412/6
z Speed limitation via setpoint 1
(NSET1-N1), if C0412/1 is
assigned, if not via max.
frequency (C0011)
C0015
uSEr
V/f rated
frequency
50.00 7.50 {0.02
Hz}
960.00 z C0015 is calculated and
stored under C0148 when
the motor parameters are
identified
z Settings applies to all
mains voltages permitted
C0016
uSEr
V
min
boost
Æ
0.00 {0.01
%}
40.00 ÆDepending on the controller
Setting applies to all mains
voltages permitted