7 Data transfer
7.2 Response of the outputs in compliance with PROFINET standard V2.3
38
Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.2 Response of the outputs in compliance with PROFINET standard V2.3
Event Response of the outputs
Switch on mains (power ON) The output data are set to '0'.
Abort of the process data transfer The output data are treated according to the parameter setting of codes
C13880/1
, C13881/0, and C13885/0.
Invalid IO controller output values The output data are set to '0'.