Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23 75
13 Parameter reference
13.1 Communication-relevant parameters of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13 Parameter reference
This chapter complements the parameter list and the table of attributes in the reference manual
and the online help for the Inverter Drive 8400 motec by the parameters for PROFINET
communication.
13.1 Communication-relevant parameters of the operating system
This chapter lists the communication-relevant parameters of the 8400 motec operating system in
numerically ascending order.
C01501
C01503
Reference manual/online help for the Inverter Drive 8400 motec
Here you will find general information on parameters.
Parameter | Name:
C01501 | Response in case of communication fault with MCI
Data type: UNSIGNED_8
Index: 23074
d
= 5A22
h
Configuration of monitoring functions for the Communication Unit
Selection list
0 No response
1 Error
4 Warning Locked
Subcodes Lenze setting Info
C01501/1 1: No Response Resp. to MCI fault 1
Response to a communication fault.
C01501/2 1: No Response Resp. to MCI fault 2
Response to a fault in the Communication Unit.
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C01503 | MCI timeout
Data type: UNSIGNED_16
Index: 23072
d
= 5A20
h
Setting range (min. value | unit | max. value)
0 ms 1000
Subcodes Lenze setting Info
C01503/1 200 ms MCI timeout
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1