12 Error messages
12.2 Possible causes and remedies
74
Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PROFINET: IP address error [0x01bc6533]
PROFINET: Stack init error [0x01bc6534]
PROFINET: Internal error [0x01bc6650]
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information
Cause Remedy
An invalid IP address has been assigned by the I/O
controller via PROFINET or has been set in code C13000
.
Make sure that the I/O controller has assigned a valid
IP address via PROFINET.
Set a valid IP address.
Setting the IP configuration
( 29)
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information
Cause Remedy
The stack cannot be initialised with the parameters
selected by the user. This may be due to a station name
which does not comply with the PROFINET specification.
Check and, if necessary, adapt PROFINET parameters:
Setting the IP configuration
( 29)
Setting the station name
( 27)
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information
Cause Remedy
Device is defective. Send the device and a description of the fault to Lenze.