Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23 73
12 Error messages
12.2 Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PROFINET: Invalid module configuration [0x01bc6430]
PROFINET: Record parameter: Invalid read [0x01bc6501]
PROFINET: Record parameter: Invalid write [0x01bc6502]
PROFINET: Data output status bad [0x01bc6503]
PROFINET: Data_Exchange status quit [0x01bc6531]
PROFINET: Station name error [0x01bc6532]
Response (Lenze setting printed in bold) Setting: C01501/2 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information
Cause Remedy
A module or submodule does not comply with the
configuration of the Siemens STEP7 engineering tool.
Check module configuration.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Invalid parameter read access Check configuration.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Invalid parameter write access
When reading back the data, the IO Controller has
requested a data length (number of data bytes) that is to
small.
Check configuration.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Output data invalid.
Connection to the Siemens STEP7 engineering tool
has been interrupted.
Check configuration.
Check cables and terminals.
Response (Lenze setting printed in bold) Setting: C13880/1 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The data exchange via PROFINET has been terminated.
Also see the chapter "Interruption of PROFINET
communication" ( 64).
Check cables and terminals.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information
Cause Remedy
Station name is not DNS-conform. Use a DNS-compliant station name.
Setting the station name
( 27)