Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23 83
13 Parameter reference
13.2 Parameters relevant for PROFINET communication
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13880
C13881
C13885
Parameter | Name:
C13880 | Monitoring Reaction
Data type: UNSIGNED_8
Index: 10695
d
= 29C7
h
The action set in subcode 1 of the code is carried out when the node recognises that it is no longer in the
"Data_Exchange" status.
Please also observe the notes provided in code C13881
.
A change in the monitoring response becomes immediately effective.
Selection list
0 No response
1 Error
3 Quick stop by trouble
4 Warning Locked
6 Information
Subcodes Lenze setting Info
C13880/1 0: No Response "Watchdog/Data Exchange" monitoring
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13881 | Reaction time delay
Data type: UNSIGNED_16
Index: 10694
d
= 29C6
h
If the "Data_Exchange" status is exited, the response parameterised in C13880 is activated after the time set here
has expired.
A value of "65535" in this code deactivates the monitoring function.
A change of monitoring will be effective immediately.
Setting range (min. value | unit | max. value) Lenze setting
0 ms 65535 0ms
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13885 | Clear process data
Data type: UNSIGNED_8
Index: 10690
d
= 29C2
h
This code is used to set the process data which the I/O device is to process in order to maintain the internal
communication when the PROFINET has exited the "Data_Exchange" status.
Selection list (Lenze setting printed in bold)
0 Use of most recent master PDOs
1 PDOs are set to the value'0'
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT