6 Commissioning
6.3 Setting the station name
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3 Setting the station name
The station name currently used is shown in code C13864.
The station name ...
is required for unambiguous addressing of the Inverter Drive 8400 motec by the I/O controller.
can either be assigned by the I/O controller via PROFINET or set manually in the »Engineer«.
has to be allocated in accordance with the PROFINET specification:
1 or several labels separated by ".".
Max. length per label: 63 characters
Max. total length: 240 characters
Permissible characters: [a ... z], [0 ... 9], [.], [-]
Labels must not begin or end with [-].
Prohibited syntax:
"n.n.n.n" (n = 0 ... 999)
"port-xyz" (x, y, z = 0 ... 9)
"port-xyz-abcde" (a,b,c,d,e,x,y,z=0...9)
Note!
The "Node blinking test" PROFINET function which serves to identify an accessible
device is supported. The red LED BE (LED status displays
( 66)) flickers during
execution.
Operation of PROFINET requires a valid station name.
In the case of impermissible settings, the red LED BE blinks (LED status displays
( 66)),
and the error message PROFINET: Stack init error [0x01bc6534]
( 74) is output. The
Communication Unit then internally continues to work with the deleted name.
If the station name is assigned by the IO controller via PROFINET or via the PROFINET
configurator of the »Engineer«, changes will become effective immediately.