6 Commissioning
6.5 Establishing an online connection via PROFINET with the Lenze »Engineer«
34
Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.5 Establishing an online connection via PROFINET with the Lenze »Engineer«
This functionality is only supported from software version V01.30.05.
[6-1] Example: PROFINET network
For an online connection between the »Engineer« and the inverter, the inverter must have an IP
address (see Setting the IP configuration
( 29)).
Note!
To ensure perfect operation of cyclic PROFINET communication, online access with the
»Engineer« must be effected via a PROFINET switch.
The PROFINET switch integrated in the communication module can execute cyclic
PROFINET communication prior to normal TCP/IP communication. In the case of
PROFINET this is effected via the VLAN identification in the Ethernet frame.