4Technical data
4.1 General data and operating conditions
16
Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4 Technical data
4.1 General data and operating conditions
"Inverter Drives 8400 motec" hardware manual
Here you will find the ambient conditions and information on the electromagnetic
compatibility (EMC) that also apply to the Communication Unit.
Range Values
Order designation • E84DGFCRxNx (PROFINET)
• E84DGFCRxJx (PROFINET + Safety)
Communication profile PROFINET
Communication medium S/FTP (Screened Foiled Twisted Pair, ISO/IEC 11801 or EN 50173), CAT 5e
Interface for communication • PROFINET port 1: M12 socket, 5-pole, D-coded
• PROFINET port 2: M12 socket, 5-pole, D-coded
Network topology Tree, star, and line
Type of node I/O device with real time (RT) communication properties
Number of device nodes Max. 255 in the subnetwork
Max. cable length between two
nodes
100 m
PNO identification number 0x0106
Device identification (Device ID) 0x8440
Baud rate 100 Mbps
Switching method "Store and forward"
Switch latency Approx. 125 μs at max. frame length
External voltage supply • U = 24 V DC (20 V - 0 % ... 29 V + 0 %)
•I
max
= 120 mA
Conformities, approvals • CE
•UR / cUR
(see also hardware manual)