9 Parameter data transfer
9.1 The acyclic channel (PROFIdrive profile)
46
Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.1.2 Acyclic data transmission process
[9-2] Data communication via the acyclic channel
A "Write.req" is used for transmitting the data set (DB47) to the I/O device in the form of a
parameter request.
"Write.res" confirms the receipt of the message by the I/O controller.
The I/O controller requests the response of the I/O device with "Read.req".
The I/O device responds with a "Read.res (-)" if processing is not yet completed.
After parameter processing, the parameter request is completed by transmitting the parameter
response in the form of a "Read.res (+)" to the I/O controller.