Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23 39
8 Process data transfer
8.1 Access to process data / PDO mapping
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8 Process data transfer
8.1 Access to process data / PDO mapping
Process data are transferred via the MCI/CAN interface.
Max. 8 words (16 bits/word) per direction can be exchanged.
The process data are accessed via the LP_Network_In and LP_Network_Out port blocks. These
port blocks are also called process data channels.
•Port block LP_Network_In maps the MCI PDOs received.
•Port block LP_Network_Out maps the MCI PDOs to be transmitted.
The port/function blocks of the process data objects (PDO) are interconnected via the Lenze
»Engineer«.
[8-1] External and internal data transfer between the bus system, inverter, and application
Reference manual/online help for the Inverter Drive 8400 motec
Here you will find detailed information on the port/function block interconnection in
the »Engineer« and the port blocks.