13 Parameter reference
13.2 Parameters relevant for PROFINET communication
84
Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13887
C13899
C13900
Parameter | Name:
C13887 | Suppress signalling diag. mess. upon
Data type: BITFIELD_8
Index: 10688
d
= 29C0
h
With this code, the transmission of alarm messages to the IO controller can be suppressed.
By setting the corresponding bit to TRUE, errors of a specific type can be suppressed systematically. In addition, all
errors are entered in the logbook.
A change can only be effective immediately if no error number with the error type selected here is active in
C00165.
Value is bit-coded: Info
Bit 0 Error
Bit 1 Fault
Bit 2 Quick stop by trouble
Bit 3 Warning Locked
Bit 4 Warning
Bit 5 Information Starting from SW version 3.00.
Bit 6 Reserved
Bit 7 Connection to 8400 lost Starting from SW version 3.00.
Error message: PROFINET: Exist. conn. to 8400 lost
[0x01bc3100] ( 71)
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13899 | Station name
Data type: VISIBLE_STRING
Index: 10676
d
= 29B4
h
The name with a max. length of 240 characters is distributed to the subindices. The name can be entered starting
with subindex 1. The following unused subindices are not relevant.
The station name must be assigned in accordance with the PROFINET specification. In the standard setting a
deleted name is displayed. The name is also deleted if the "Reset to factory defaults" command is executed by an
IO supervisor or an I/O controller.
A change of the station name will only become effective by switching the mains of the inverter.
Setting the station name
( 27)
Subcodes Lenze setting Info
C13899/1 1st ... 30th character
C13899/2 31th ... 60th character
C13899/3 61th ... 90th character
C13899/4 91th ... 120th character
C13899/5 121th ... 150th character
C13899/6 151th ... 180th character
C13899/7 181th ... 210th character
C13899/8 211th ... 240th character
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13900 | Firmware Product Type
Data type: VISIBLE_STRING
Index: 10675
d
= 29B3
h
The code contains a string with a length of 8 characters. The identification code "E84DGFCR" is output.
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT