Commissioning
Configuring the digital inputs and outputs
Change of the terminal assignment
6
123
EDBCSXS064 EN 4.0
Code Possible settings IMPORTANT
No. Designation Lenze/
{Appl.}
Selection
C3005 ControlMode 0
Selection of operating modes 126
0 Common Display with changed standard
application
100 None Reset of all signal connections
1000 SpeedTerm Speed−controlled, setpoint via
analog input
318
1003 SpeedAIF Speed−controlled, setpoint via
AIF
1005 SpeedCAN Speed−controlled, setpoint via
MotionBus (CAN)
4000 TorqueTerm Torque−controlled, setpoint via
analog input
343
4003 TorqueAIF Torque−controlled, setpoint via
AIF
4005 TorqueCAN Torque−controlled, setpoint via
MotionBus (CAN)
[C6371] Selection of the digital output
signals for the digital output and
the brake relay
308
1 DigoutIn−dig 1000 0 (FALSE, not assigned) Source for the output signal at
the digital output X6/DO1
(DigOut−Out1)
2 DigoutIn−dig 1000 0 (FALSE, not assigned) Source for the control of the
brake relay (DigOut relay)
For possible signals see "selection list − digital
signals"
428