Appendix
Code table
13
381
EDBCSXS064 EN 4.0
IMPORTANTPossible settingsCode
SelectionLenze/
{Appl.}
DesignationNo.
C0349 Status of the DIP switch for CAN
bus interface X4
Read only
1 CAN DIP−SW 0 {1} 63 Node address set on the DIP
switch
2 CAN DIP−SW 0 4 For setting the DIP switches > 4,
the display is set to 0.
C0350 CAN address 32 Node address for CAN bus
interface X4
l This code is not active if one
of the switches 2 ... 7 of the
DIP switch is set to "ON".
( 169)
l After the setting process, a
reset node is required.
l A definite node address must
be assigned to each CAN
node.
169
460
1 {1} 63
C0351 CAN baud rate 0 Baud rate for CAN bus interface
X4
l The baud rate must be set
identically for all CAN nodes.
l This code is not active if one
of the switches 2 ... 7 of the
DIP switch is set to "ON".
l After the setting process, a
reset node is required.
169
0 500 kbps
1 250 kbits/sec
2 125 kbit/s
3 50 kbps
4 1000 kbit/s
C0352 CAN mst 0
Boot−up master/slave
configuration for CAN bus
interface X4
175
0 Slave
1 Master boot−up Device is active as CAN boot−up
master.
2 Master node guarding
3 Slave heartbeat producer
4 Slave node guarding
C0353 Source for node address of
CAN_IN/CAN_OUT (CAN bus
interface X4)
173
1 CAN addr sel 0 CAN node address (C0350) Address CAN1_IN/OUT
2 CAN addr sel 0 CAN node address (C0350) Address CAN2_IN/OUT
3 CAN addr sel 0 CAN node address (C0350) Address CAN3_IN/OUT
0 C0350 (auto) Automatically determined by
C0350.
1 C0354 (man.) Determined by C0354.