Commissioning
Configuration with internal DIP switches
Settings in the operating mode (normal operation)
7
l
63
EDBMZ9374X DE/EN/FR 4.2
Setting the CAN bus baud rate
DIP switch Baud rate [kBit/s]
1000 500 250 125 100 50 20 10
9 OFF OFF OFF OFF ON ON ON ON
10 OFF OFF ON ON OFF OFF ON ON
11 OFF ON OFF ON OFF ON OFF ON
ƒ Set the baud rate of the terminal extensions with the DIP switches 9 ... 11.
The baud rate of the terminal extension must be identical with the baud
rate of the controller (master).
In the Lenze default setting, the master has the baud rate 500 kBit/s
(C0351 = 0).
) Note!
The baud rate to be set depends on the length of the system bus
cable. ( 50, Technical data)