Commissioning
Configuration with internal DIP switches
Settings in the operating mode (normal operation)
7
l
62
EDBMZ9374X DE/EN/FR 4.2
) Note!
Note that the address of the terminal extension must one value
higher than the address of the controller.
ƒ In the Lenze default setting, the master has address 1 (C0350 = 1).
In this case, set the terminal extension to address 2.
Number of terminal extensions used
9374 9374 9374 9374
CAN
CAN CAN CAN CAN
9374-Master 9374-Slave1 9374-Slave2 9374-Slave3
SlaveMaster
9374_012
ƒ The terminal extension 9374−master communicates with the controller
(master).
ƒ Three more terminal extensions can communicate with the 9374−master
as slaves via the system bus.
DIP switch Number of terminal extensions
1* 2 3 4
7 OFF ON OFF ON
8 OFF OFF ON ON
*
Terminal extension is always "9374−master"