Installation
Electrical installation
Wiring the CAN bus
5
Ò
53
EDSMDAG EN 2.0
Interferences on the CAN bus
In case of interferences on the CAN bus, a shielded cable must be used. The shield is
connected to PE (chassis ground). The shield/PE connection must have a low resistance to
avoid shield currents in the system.
ƒ Connect the shield on one side to PE.
ƒ Connect the shield on both sides to PE if interferences continue to occur in case the
shield is only connected on one side.
High
Low
CAN
HCU
CAN
MOBILE 1
CAN
MOBILE 2
+
+
EMDAG0034b