No. Designation min. max. Default Unit r/w Format Description
132 Limit temperature 0 140 * °C r u16 Maximum permissible pump housing temperature,
pump housing P125>P132 will shut the pump down.
171 Error code memory for 0 255 0 r u16 Sequential permanent memory; the individual error
the 40 most recent events codes are accessed via parameter 171 with
additional index no. in the parameter order
identifier of the interface protocol.
The last error code which has occurred
is saved at the memory location with the
index 0, the oldest is at index 39.
See Section 3.2.10 for the error codes.
174 Stator frequency at the 0 P18 0 Hz r u16 Analogously as for P171
time of error (error code memory)
176 Error operating hours 0
memory for the 40 most 2147483647 0 0.01 h r u32 Analogously as for P171
recent error events (error code memory)
179 Response when cancelling 0 65535 0 r/w u16
the control rights or in the
case of a communication
interruption of the bus adapter
Behaviour in case bit 10 in the control word of the bus adapter is cancelled or when interrupting the communication between con-
verter and bus adapter (see also P182). Here it is assumed that the respective bus adapters perform a cyclic communication on
the USS side, so that the respective converter electronics is capable of detecting a communication interruption
The bits in parameter 179 represent an equivalent to the control word in the USS protocol.
The actions linked to these bits are run provided bit 10 in the control word (USS protocol for bus adapter) is cancelled or if there
are interruptions in the communication between converter and bus adapter.
Here bit 10 is of special significance:
Bit 10 = 0 The control rights are returned to the next lower priority level. All other bits are not relevant.
Bit 10 = 1 The control rights remain unchanged. The actions linked to the other bits are run.
180 Response delay time 2 19 10 ms r/w u16 Pause time between received string and the
subsequent reply string (minimum interval)
181 Bus adapter baud rate 48 576 192 100/s R/W u16 Baud rate for RS 232/RS 485 options board,
respectively internal baud rate for other bus
adapter values:
48 = 4800 baud
96 = 9600 baud
192 = 19200 baud (standard)
288 = 28800 baud
576 = 57600 baud
182 Delay when cancelling the 0 65535 10 0.1 s r/w u16
control rights of the bus
adapter and time-out in the
case of a communication
interruption
Defines the time characteristic when cancelling bit 10 in the control word of the USS protocol or when an interruption in the com-
munication between bus adapter and converter and electronics is detected. Handling when cancelling bit 10 or when there is an
interruption on the communication side of the USS bus adapter, is the same.
Value 0.0: Indefinite time delay. In this way a change of the control right is inhibited.
Values 0.1 ..6553.5: A change in the control right corresponding to the setting of parameter 179 is only effected after the time
span defined through parameter 182 has elapsed.
Operation
25