18 | PRODUCT DATA
Single Zone High Efciency, Standard and Extended Pipe Wall Mount Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
ELECTRICAL DATA
Model Number Nom. Tons Compressor Qty
Compressor (A)
Cool/Heat
Fan Qty ODU Fan (A) MCA (A) MOP (A)
LSU091HSV3
3/4 1 8.7/8.7 1 0.40 10 15
LSU121HSV3
1 1 8.7/8.7 1 0.40 10 15
LSU181HSV3
1-1/2 1 15.4/15.4 1 0.25 19 25
LSU240HSV3
1-3/4 1 15.4/15.4 1 0.25 19 25
Table 9: Single Zone High Efciency Unit Electrical Data
Model Number Nom. Tons Compressor Qty
Compressor (A)
Cool/Heat
Fan Qty ODU Fan (A) MCA (A) MOP (A)
LSU307HV3
2-1/2 1 15.4/15.4 1 0.25 19 25
LSU360HV3
2-3/4 1 15.4/15.4 1 0.25 19 25
Table 10: Single Zone Standard Unit Electrical Data
Model Number Nom. Tons Compressor Qty
Compressor (A)
Cool/Heat
Fan Qty ODU Fan (A) MCA (A) MOP (A)
LSU240HLV
1-3/4 1 17.3/17.3 1 0.25 23 35
LSU300HLV
2-1/2 1 17.3/17.3 1 0.25 23 35
LSU360HLV
2-3/4 1 17.3/17.3 1 0.25 23 35
Table 11: Single Zone Extended Pipe Unit Electrical Data