CONFIGURATION SCREENS
Parameter Parameter Settings Denition
Setpoint cool Range: 50-99 °F
Default value: 78°F
Range of cooling setpoint values
Setpoint heat Range: 40-90 °F
Default value: 68°F
Range of heating setpoint values
System mode Choices: Off, Cool, Heat, Fan, Auto, Dry
Default value: OFF
System modes
Fan Speed Choices: Slow, Low, Low-Med, Medium,
Med-High, High, Power, Auto
Default value: Low
Fan speed settings
Occ./Unocc. Choice: Unoccupied, Occupied
Default value: Unoccupied
Selection of unoccupied or occupied for the
conditioned space
Daily Schedule Screens – continued
H 74 / 70:O
To modify an existing
event, tap either the
left side control to
edit the time or tap
the right-hand side of
the control to re-enter
the event screen and
make your desired
changes.
If desired, use the
'Copy to' button to
copy the schedule
to another day of
the week. First
choose the time of
the event you want
to copy and then
choose ‘Copy to’.
To delete an event,
tap the time of the
event and then tap
the Delete button.
Choose the day(s)
you want to copy the
event to and then
press the left arrow.
Event Overview Display Parameter Meaning
First Letter Mode (O=off, C=cool, H=heat, F=fan, A=auto, D=dry)
Second Number(s) Set Point(s)
Third Letter Occupancy Status (U=unoccupied, O=Occupied)
Current Example: H: 74 / 70: O = Heating Mode, Upper setpoint of 74, Lower setpoint of 70, Occupied