MultiSITE CRC 1 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
Setpoints Configuration
Press the Setpoint Cong button on the Building
Manager Screen to display the Setpoints Conguration
screen. Press the Single/Dual button to select single or
dual setpoint operation.
Note: If changes are made to Deadband and Setpoint
Min/Max values after scheduled events have already
been added to the Schedule Event table, the new rules
will be enforced only when the user enters back into the
Schedule Editor.
If setpoint max./min. values are not visible, this indicates
that central control (CC) has issued a command for more
restrictive values and that the CRC1 is now following
CC. To re-enable these controls, CC limits must exceed
values of remote controller.
Setpoint Single / Dual 1/2
Single / Dual Dual SP(1)
Setpoint Single / Dual 2/2
Setpoint Max.
86.0 °F
Setpoint Min.
60.0 °F
Single Setpoint Mode
Press up or down arrow
keys below to select
between Single or Dual
set point modes.
Note: Available functions/
features may differ based
on the connected system.
Setpoints Config. 2/2
Cooling SP Max
99 °F
Cooling SP Min
52 °F
Heating SP Max
90 °F
Heating SP Min
40 °F
Min. deadband
4 °F
Dual Setpoint Mode
Minimum deadband value
between the heating and cooling
setpoints. Applied only when any
of the setpoints are modied.
Range is 1 °F - 10 °F
Parameters / Default Value Parameter Settings
Single/Dual
Default value: Dual SP(1)
Default value can be changed by user
Single SP
(Single Setpoint Adjustment)
Setpoint Maximum is 86 °F
Setpoint Minimum is 60 °F
Dual SP
(Dual Setpoints Adjustment)
Maximum upper cooling temperature is 99 °F
Minimum lower cooling temperature is 50 °F
Maximum upper heating temperature is 90 °F
Minimum lower heating temperature is 40°F
Deadband range is 1 °F - 10 °F

Other manuals for LG MultiSITE CRC1 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG MultiSITE CRC1 Series and is the answer not in the manual?

LG MultiSITE CRC1 Series Specifications

General IconGeneral
BrandLG
ModelMultiSITE CRC1 Series
CategoryRemote Control
LanguageEnglish

Related product manuals